System Sensor™ Smoke Sensor Model 2100ARFT
Installation Instructions
Product Summary
The System Sensor Smoke Sensor Model 2100ARFT
(smoke alarm) is a Learn Mode, wireless, photoelectric
smoke sensor with a self-contained alarm siren, a low-bat-
tery annunciator, and a status light. The smoke alarm is part
of a security/fire alarm system and communicates with the
system control panel.
Each smoke alarm uses two 3-volt lithium batteries. The
batteries are shipped in the unit with a pull tab inserted at
the positive terminal. Remove the pull tab and reinstall the
batteries as needed, observing correct polarity.
The detector provides the following features:
Fixed/rate of rise 135° F temperature heat detector
trips an alarm when the temperature reaches 135° F or
higher, or when the temperature rises rapidly.
Freeze detector sends a trouble signal when the ambi-
ent temperature around the detector drops below 40° F.
This could indicate a heating problem on the premises.
System sirens sound trouble beeps, and if the condition
continues for one hour, the panel reports to central
monitoring station.
Note
Freeze detector only compatible with Concord™, Con-
cord Express, Ultragard
®
, and Advent
®
systems.
Simon
®
systems will only respond on site with trouble
beeps and will not report the trouble condition to the
central monitoring station.
Installation Guidelines
This equipment should be installed in accordance with
the National Fire Protection Association’s Standard 72
and/or Standard 74 (National Fire Protection Associa-
tion, Batterymarch Park, Quincy, MA 02269).
Avoid installing the unit until all construction is com-
pleted. The mounting ring may be pre-installed.
Leave the orange dust cover on the unit until sheet
rocking and sanding are completed; otherwise, dust can
get into the unit and cause false alarms.
Note
The orange dust cover must be removed for the unit to
detect smoke.
CAUTION
Not compatible with CareTaker
®
Plus
and custom
versions with software versions 3.0 or earlier.
Not compatible with Commander
®
2000 and custom
versions with software versions 4.0 or earlier.
Equipment Needed
Phillips screwdriver.
Pocket-sized slotted screwdriver.
Programming
This section describes the basic steps for adding the sensor
to panel memory. For more detailed programming informa-
tion, refer to the specific panel installation instructions.
Figure 1. Mounting Bracket
To add the smoke alarm to panel memory:
1. Put the panel in Program Mode/Learn Sensors.
2. Select a sensor group and sensor number.
3. Remove mounting bracket to trip tamper.
4. The panel will indicate that the sensor has been
learned.
5. Exit from program mode.
Note
Reinstall smoke unit on mounting bracket. This
restores the tamper to normal—it may take the micro-
processor in the smoke unit up to 12 seconds to
restore the tamper.
Mounting Guidelines
Selecting a suitable location is critical to the operation of
smoke alarms/detectors. This equipment should be installed
System Sensor™ Smoke
Sensor Model 2100ARFT
ITI Part No. 60-838-95, 60-838-95R
Document Number: 466-1747 Rev. C
September 2000
Page view 0
1 2 3 4 5 6 7

Summary of Contents

Page 1 - Sensor Model 2100ARFT

1System Sensor™ Smoke Sensor Model 2100ARFTInstallation InstructionsProduct SummaryThe System Sensor Smoke Sensor Model 2100ARFT (smoke alarm) is a Le

Page 2 - Important !

2System Sensor™ Smoke Sensor Model 2100ARFTMounting Guidelinesin accordance with the National Fire Protection Associa-tion’s (NFPA) Standard 72, Chapt

Page 3 - Mounting

3System Sensor™ Smoke Sensor Model 2100ARFTMounting❑ Put a smoke alarm on every level of a multi-level resi-dence.❑ Install basement alarms on the cei

Page 4 - Emergencies

4System Sensor™ Smoke Sensor Model 2100ARFTMaintenanceNoteSimon and Advent panels respond to test button acti-vations only when in sensor test mode.WA

Page 5 - Your Floor Plan

5System Sensor™ Smoke Sensor Model 2100ARFTEmergencies❑ Meet at a designated outdoor location.❑ Emphasize that no one should return to the premises if

Page 6

6System Sensor™ Smoke Sensor Model 2100ARFTEmergenciesDraw you floor plan in this space.

Page 7 - Troubleshooting

7System Sensor™ Smoke Sensor Model 2100ARFTTroubleshootingTroubleshootingThe panel fails to indicate that the sensor has been learned.❑ Check panel pr